Welcome to Shanghai HanKing Instrument & Equipment Co.,Ltd
Product Category
Temperature and Humidity Transmitter
Temperature and Humidity Transmitter
Equipped with interchangeable probe inputs or fixed/integrated probes, provide highly accurate analog or digital output measurements for a wide range of industrial applications—including process monitoring and control, cleanrooms, controlled environments, data centers, building management systems, storage areas, swimming pools, museums and art galleries, and many others.
| HF1 Series
The HygroFlex1 series is a new, cost-effective transmitter
for measuring relative humidity and temperature in the
HVAC field. The HF1 is equipped with the Hygromer® IN-1 sensor and offers exceptional value for money. By selecting the optional HW4 software, you can adjust the measurement range and calibrate and characterize the transmitter
Feature
√ 23℃ ±5℃ accuracy: ±2%RH / ±0.3℃; ±1.5%RH / ±0.2℃ (upgraded version)
√ Measurement range: -20~60℃ / 0~100%RH
√ Compact size, easy to install
√ USB port
√ Factory calibration: 35% RH, 80% RH

| HF3 Series
The HygroFlex3 series transmitters are suitable for applications requiring precise measurement of temperature and humidity. From the HVAC industry to greenhouses and museums, from storage rooms and libraries to subways and office environments, the HF3 series transmitters can meet all these needs.
Feature
√ 23℃ ±5℃ accuracy: ±2%RH / ±0.2℃
√ Measurement range: -40~60℃ / 0~100%RH
√ Operating range: -40~60℃ / 0~100% RH, with display: -10~60℃
√ Analog output can be software-configured.
√ Configuration interface
√ Three-point calibration at 23℃, 10%, 35%, and 80% RH
√ Dew point output

| HF5 Series
The HygroFlex5 series is compatible with all HC2 probes equipped with the AirChip chip. Thanks to the high precision of these probes, the HF5 series transmitters are capable of performing highly accurate measurements. This transmitter series features several innovative technologies that make parameter setting and calibration exceptionally convenient.
Feature
√ Up to two interchangeable HC2A probes
√ Accuracy: ±8% RH and ±0.1℃ at 10–30℃ (commonly used accuracy)
√ Measurement range: -50~100℃ / 0~100%RH (commonly used range)
√ Operating range: -40~60℃ / 0~100% RH, with display: -10~60℃
√ Digital output can be used in combination with analog output.
√ Can be used as a system verification simulator (requires operation via HW4 software and communication cable).
√ Configuration interface

| CRP5 Series
The CRP5 cleanroom panel is equipped with a diaphragm sensor for differential pressure measurement, offering excellent performance. The CRP5 features both analog and digital communication capabilities, making it easy to integrate into any monitoring system. It meets GMP validation requirements, has been carefully designed, and is specifically optimized for laboratory and cleanroom applications.
Feature
√ Specifically designed for sterile rooms
√ The detachable temperature and humidity probe makes adjustment and cleaning easier.
√ Compatible with FDA 21 CFR Part 11 and GAMP
√ Accuracy: Pressure ±1.0%FS; Temperature ±0.2℃; Humidity ±1.5%RH
√ Digital communication via Ethernet RJ45 or TCP/RTU network communication protocols
√ Analog and digital signal input
√ The front panel features a differential pressure measurement and calibration interface.
√ Relay or color TFT alarm
√ Highly corrosion-resistant glass front panel

| HygroFlex5-EX
The HygroFlex5-EX series consists of a dual-channel transmitter, a product specifically developed for precise measurement of temperature and humidity in explosive environments, and complies with international standards. The ROTRONIC HF5-EX series transmitters feature a robust aluminum housing and come equipped with a display. Paired with a durable stainless steel probe, they can be used in Zone 0/Zone 20.
Feature
√ Measure relative humidity and temperature
√ Accuracy: ±8% RH and ±0.1℃ at 10~30℃
√ Can output dew point and other psychrometric calculation parameters
√ Can operate safely in hazardous explosive areas
√ Intrinsically Safe Circuit Design
√ No intrinsically safe power supply required
√ Interchangeable stainless steel probe
√ Two temperature certifications (T4/T5)

| HF1 / HF3
|
|
HF1 |
HF3 |
|
Type |
Fixed probe |
|
|
Application |
HVAC |
|
|
Scope of work |
-20-50 Celsius / 0-100 %RH |
-40 to -60 Celsius / 0-100 %RH |
|
Accuracy @ 23 Celsius |
±2% RH (10-90% RH) / ±0.3 K |
<±2 %RH / ±0.3 K |
|
Long-term stability |
<1.5% rH/ Year |
<1% RH/ Year |
|
Sensor |
Humidity: Rotronic IN1 / Thermistor |
Humidity: Rotronic IN1 / PT100 A Level |
|
Show |
Optional with or without |
|
|
Power supply |
12-28 VAC / 15-40 VDC |
HF32 2 Line: 10-28 VDC HF33 3/4 Line: 18–40 VDC / 13–28 VAC |
|
Output parameter |
Humidity and temperature |
Humidity and temperature |
|
Output |
2 An analog output 2 Line or 3/4 Line, freely expandable |
|
|
Output signal |
2 Line: 4-20 mA 3/4 Line: 0(4)-20 mA 0–1/5/10 VDC |
|
|
Housing type |
Wall mounting and pipe installation |
Wall-mounted, pipe and wall installation |
|
Housing material |
ABS |
|
|
Size |
Wall-mounted 105x172 mm |
Wall-mounted 101x182 mm |
| CRP5 Series
|
|
CRP5 |
|
Accuracy @ 23 ±5 Celsius |
±1.0% Full scale (Pa) |
|
Parameter |
Differential pressure, temperature, humidity, digital and analog outputs |
|
Probe |
HC2-CRP ; Replaceable: Any HygroClip2 Probe |
|
Scope of application |
-5...60 Celsius (23...140°F) / 0...100% RH |
|
Measurement principle |
Diaphragm sensor |
|
Measurement range |
±50 Pa / ±100 Pa / ±250 Pa / ±500 Pa & -100...200 Celsius ( Depends on the probe. ) / 0...100 %RH |
|
Withstand voltage |
0.7 bar (70,000 Pa) |
|
Pressure connection |
Front: Hose connector Ø 6 mm x 10 mm Next: Hose connector Ø 4 mm x 10 mm |
|
Medium |
Air and non-corrosive gases |
|
Precision analog output |
±5 mV ( Voltage output ) ±20 mu A ( Current output ) |
|
Digital output |
6 Solid-state relay for roads |
|
Switched-capacitor |
<50 VDC @ <2A , when considering polarity <35 VAC @ <1A , without considering polarity |
|
Zero drift |
Compensation ( Manual or automatic zero adjustment ) |
|
Power consumption |
20...48 VDC / 18...35 VAC <500 mA |
|
Display type |
Colorful TFT Show |
|
Electrical connection |
On the back screw terminal |
|
Measurement interval |
1 s |
|
Menu Navigation |
4 An optical key |
|
Software update |
Through HW4 Software |
|
Analog output |
4 The path can be freely configured. |
|
Analog output signal ( Standard ) |
0 / 4...20 mA or 0...1 / 5 / 10 V |
|
Communication interface |
Ethernet (Modbus TCP, HW4) / RS-485 (Modbus RTU, HW4) |
|
Permissible load |
>10 kΩ ( Voltage output ) <500 Ω ( Current output ) |
|
Fire rating |
Compliant UL94-HB |
|
Shell |
Front panel: Glass Back panel: Steel plate |
|
IP Protection level |
Front: IP65 ( Sensor removed ) Behind: IP20 |
|
Install |
Wall-mounted |
|
Service interface |
UART |
|
FDA / GAMP |
FDA 21 CFR Part 11 / GAMP5 |
|
CE / EMC Consistency |
EMC Instruction 2004/108/EC |
|
Storage and Transportation Conditions |
-5...60 Celsius (23...140°F) / 0...100% RH |
|
Size |
180 x 300 x 72 mm |
|
Weight |
1,700 g ( With humidity sensor ) 1,550 g ( Does not include a humidity sensor ) |
| HF5 / HF5-EX
|
|
HF5 |
HF5- EX |
|
Order number |
|
HF520 EX |
|
Type |
1x Interchangeable HC2A Probe |
|
|
Application |
Pharmaceutical industry |
Oil, natural gas, steel mills |
|
Scope of work |
-40 to -60 Celsius / 0-100 %RH ; -10-60 °C display |
|
|
Measurement range |
-100-200 Celsius / 0-100 %RH , depending on the specific probe |
|
|
Compatible probe |
HC2A-S Series, HC2A-IC/IM/IE,HC2-CP,HC2-HK |
HC2-SM-EX / HC2-IM-EX / HC2-IE-EX / HC2-LDP-EX |
|
Probe cable length |
5m Passive; accessible 100m Active cable |
2/5/10 m |
|
Accuracy @ 23°C |
±0.8 %RH / ±0.1 K ( Normal value ) , depending on the specific probe |
|
|
Long-term stability |
<1 %RH ( Normal value ) , depending on the specific probe |
|
|
Sensor |
Depends on the specific probe. |
|
|
Show |
Optional with or without |
|
|
Power supply |
HF52 2 Line: 10-28 VDC HF53 3/4 Line: 15–40 VDC / 12–28 VAC HF54 Current isolation 9…36 VDC HF56 Current isolation 100-240 VAC |
10…28 VDC |
|
Output parameter |
Humidity and temperature |
|
|
Calculation parameters |
All humidity value calculations |
|
|
Output |
2 An analog output 2 Line or 3/4 Line, optionally with freely expandable digital output (LAN. RS-485) |
2 One analog output, 2 Line |
|
Output signal |
2 Line: 4-20 mA , 3/4 Line: 0(4)-20mA , 0–1/5/10 VDC |
2 Line 4…20 mA |
|
Housing type |
Wall-mounted and duct-mounted installation |
|
|
Housing material |
ABS |
Aluminum |
|
Size |
Wall-mounted 160x206 mm (with 🛡️) HC2A-S ) |
Wall-mounted 160x210 mm (Contains HC2-SM-EX ) |